Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-91-PS 2-87-PS 3-87-PS 4-Diesel-PS <br /> Sump Manufacturer Western FG Western FG Western FG Western FG <br /> Sump Depth (inches) 47" 47 1/2" 47" 49" <br /> Sump Bottom to Top of 13" 13" 23" 12" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:42 8:47 9:32 8:52 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:12 9:17 10:02 9:22 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer OPW OPW OPW OPW <br /> Sump Depth (inches) 33 1/2" 33 1/2" 33 1/2" 33 1/2" <br /> Sump Bottom to Top of 15" 17" 15 1/2" 21" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:57 9:02 9:37 9:42 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:27 9:32 10:07 10:12 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />