Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ❑ Hydrostatic <br /> Test Equipment Used:ineon Tester <br /> Sump/UDC ID uoc 1/2 uoc 314 UDC 516 <br /> Sump Manufacturer Environ Environ Environ <br /> Sump Depth (inches) 31Z 31" 31" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 162 16" 16" <br /> (inches) <br /> Test Start Time 12:02 pm 2:33 pm 10:18 am <br /> Initial Reading 4.9589 6.6620 2.7740 <br /> Test End Time 12:17 pm 2:48 pm 10:33 am <br /> Final Reading 4.9572 6.6616 2.7722 <br /> Change in Reading 0.0017 0.0004 0.0018 <br /> as Fail Criteria 0.002 0.002 0.002 <br /> Tightness Test Results CI Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ P�assFail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />