Laserfiche WebLink
TAI T <br /> gt11N <br /> TOT"SNI. Dupont Drive. <br /> P 714'56018222 www tail corn <br /> SUMMARY TEST REPORT FOR USE WITH LEIGHTON O'BRIEN PM2 LINE TESTER <br /> CLIENT: AT&T UE042 DATE: 7121/2025 <br /> LOCATION: 345 North San Joaquin St. Stockton California 95202 <br /> sheet Cky Stale <br /> REASON FOR TEST. AT&T Request.System Integrity test.Local CUPA on site Fred Ernest. <br /> SPECIAL INSTRUCTIONS: Above ground pressurized line.Leighton O'Brian Diagnostic Report Number U8177207 <br /> I declare under penalty of pedury that I am a licensed tank tester In the State of <br /> California and that the Information contained In this report Is true and correct to the <br /> beet of MX knowled e. <br /> TECHNICIAN: Pat Banbury 90-1415 <br /> Name ,. Signature License Number <br /> MAKE AND TYPE OF PUMP OR DISPENSERS Transfer Pump <br /> COVER OVER LINES Above Ground APPROX. BURIAL DEPTH NA <br /> Product Name Line Test Wet Test Start Test End Test Cert No. Test Results <br /> or Dry Time Time Pressure <br /> Diesel Basement Pass <br /> Pump To Belly WET 7:14 AM 7:52 AM 51.34 PSI 435168 0.010 gal/hr. <br /> Tank UE042AOOS <br /> T-- <br /> COMMENTS: Test conducted from the basement transfer pump room to the UE042AO05 roar top belly tank. <br /> Above ground double wall atssl piping. <br /> Note:These results need to be submitted with the final Leighton O'Brien UPSS Test Report. <br />