Laserfiche WebLink
Program Element: 2308 - UST RETROFIT <br />Telephone: (310) 997-5326 Requestor: TIM MCELHENY, TAIT ENVIRONMENTAL SERVICES <br />Inspection Type: 298 - UST SERVICE REQUEST - FIELD ACTIVITY <br />Address: 345 N SAN JOAQUIN ST , STOCKTON 95202 <br />Date: 11/13/2023Name of Facility: AT&T CALIFORNIA - UE042 <br />Underground Storage Tank Program Service Request Inspection Report <br />Request #: SR0087197 <br />Environmental Health Department <br />Onsite Service Technician: Jaime Jauregui ICC Service Tech/Installer Exp. Date: 07/25/2024 <br />Manufacturer training: VR, 09/07/24 <br />OVERALL INSPECTION NOTES AND COMMENTS <br />NOTES <br />Witnessed diesel tank replace ATG probe with float kit measurement , external audible/visual alarm activates when tank is <br />90% full. <br />Service technician stated no ball floats installed. <br />This facility is approve to receive fuel in the diesel tank. <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. <br />The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br />Safety Code. If a reinspection is required, fees will be assessed at the current hourly rate. <br />Received by: Name and Title: <br />EH Specialist:Phone:(209) 616-3049 <br />Email report to: AT&T Hot line, Enviro <br />PAUL NSO <br />Page 1 of 1EHD 23-01 Rev. 07/05/2022 Underground Storage Tank Program Service Request Inspection Report <br />FA0003959 SR0087197 SC298 11/13/2023