Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUN r <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> BlackHawk Petroleum Inc. 5611 E WATERLOO RD, STOCKTON July 19, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to document all the alarms from the attached alarm history on <br /> multiple designated operator inspection report and failed to check that they were responded to appropriately. The <br /> missing alarms include the following sensor out alarms: <br /> *L1 (87 STP sump sensor)on 4/7/23. <br /> *L2(87 annular sensor)on 4/7/23. <br /> *L3(91 STP sump sensor)on 2/12/23, 3/23/23, 3/27/23, and 4/10/23. <br /> *L4(diesel STP sump sensor)on 2/13/23, 3/23/23,4/9/23, and 4/10/23. <br /> *L5(diesel/91 annular sensor)on 4/5/23 and 4/7/23. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall review the alarm history since the <br /> previous inspection, check that each alarm was documented and responded to appropriately, and attach a copy of <br /> the alarm history with documentation taken in response to any alarms to the inspection report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports.The incorrect and missing information included the following from the inspection reports: <br /> -Owner/operator printed name was left blank. <br /> -The box for mechanical floats in the UDCs was not marked. <br /> -The question regarding alarms since the previous inspection was marked N/A when alarms had occurred. <br /> REGULATION GUIDANCE: During the visual inspection,the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> OBSERVATION: The designated operator failed to visually inspect the tank top sumps for leaks,water, debris, or <br /> other issues during the visual inspections despite there being multiple alarms. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall visually inspect all spill containers, <br /> fill pipes,fill caps, and UDC sumps, and any tank top sump that had an alarm for which there is no record of a <br /> service visit,for damage, and for the presence of leaks,water, or debris, and check that the sensors are located <br /> properly. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are inspecting all of <br /> the required areas and noting it on the on the reports. <br /> This is a repeat violation, Class II. <br /> FA0002160 PR0231764 SCO01 07/19/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />