Laserfiche WebLink
www.hilti.com <br />Hilti PROFIS Engineering 3.0.68 <br />Input data and results must be checked for conformity with the existing conditions and for plausibility! <br />PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan <br />6 <br />Company: <br />Address: <br />Phone I Fax: <br />Design: <br />Fastening point: <br />ABS Consulting <br />300 Commerce, Suite 150 <br />714-734-2583 | <br />Leprino Tracy - PRU1 <br />Page: <br />Specifier: <br />E-Mail: <br />Date: <br />6 <br />T. Rich <br />trich@absconsulting.com <br />4/2/2021 <br />4.2 Pryout Strength <br />Vcp = kcp [(ANcANc0)y ed,N y c,N y cp,N Nb ] ACI 318-14 Eq. (17.5.3.1a) <br />f Vcp ³ Vua ACI 318-14 Table 17.3.1.1 <br />ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) <br />ANc0 = 9 h2 <br />ef ACI 318-14 Eq. (17.4.2.1c) <br />y ed,N = 0.7 + 0.3 (ca,min1.5hef)£ 1.0 ACI 318-14 Eq. (17.4.2.5b) <br />y cp,N = MAX(ca,mincac <br />, 1.5hefcac)£ 1.0 ACI 318-14 Eq. (17.4.2.7b) <br />Nb = 16 l a √f' <br />c h5/3 <br />ef ACI 318-14 Eq. (17.4.2.2b) <br />Variables <br />kcp hef [in.]ca,min [in.]y c,N <br />2 12.000 12.000 1.000 <br />cac [in.]kc l a f' <br />c [psi] <br />∞ 16 1.000 4,000 <br />Calculations <br />ANc [in.2]ANc0 [in.2]y ed,N y cp,N Nb [lb] <br />900.00 1,296.00 0.900 1.000 63,648 <br />Results <br />Vcp [lb]f concrete f seismic f nonductile f Vcp [lb]Vua [lb] <br />79,560 0.700 1.000 1.000 55,692 3,237