Laserfiche WebLink
JONES COVEY GROUP, INC. <br /> COMPLETE FUEL SYSTEM CONSTRUCTION Ft MAINTENANCE SERVICES <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Pilot 1017 Lathrop DATE: 0 8 8 + 2 0 2 3 <br /> State Facility# CONTACT: Manager <br /> 1017 PHONE: (865) 588-7488 <br /> JOB#: 2367421-1-1 <br /> Tank # T3 T4 T5 T6 T7 T8 T9 T10 <br /> Product Biodiesel Biodiesel <br /> LD Manufacturer VMI VMI <br /> LD Model 99 LD-3000 99 LD-3000 <br /> Sump Condition Good Good <br /> Operation Pressure 35 PSI 40 PSI <br /> PSI <br /> Opening Time(Sec) 8 Seconds 10 Seconds <br /> Metering Pressure 15 PSI 18 PSI <br /> (PSI) <br /> Functional Element 34 PSI 37 PSI <br /> Holding Pressure <br /> Leak Rate LD Detected 3 GPH 3 GPH <br /> (GPH) <br /> Does LD Detect 3 GPH Yes Yes <br /> Leak Rate? <br /> LD Serial 30001072 30001073 <br /> Comments: <br /> Technician Keith Henderson License Number VMI -3248 <br /> Signature <br /> 9595 LUCAS RANCH ROAD, RANCHO CUCAMONGA,CA 91730- LICENSED IN 41 STATES <br /> California State License#804431 A, B, HAZ <br />