Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ® Manufacturer ® Industry Standard ® Professional Engineer <br /> Test Type ® Pressure ® Vacuum ® Hydrostatic <br /> Test Equipment Used: OMNTEC Proteus'CLD <br /> Sump/UDC ID 87 STP 91 STP Diesel STP <br /> Sump Manufacturer Fiberlite Fiberlite Fiberlite <br /> Sump Depth (inches) 48 52 46 <br /> Sump Bottom to Top of 18 18 17 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 13:15 13:15 13:15 <br /> Initial Reading 4.934 15.166 14.011 <br /> Test End Time 13:30 13:30 13:30 <br /> Final Reading 4.934 15.166 14.011 <br /> Change in Reading 0.000 0.000 0.000 <br /> Pass/Fail Criteria +/- 0.002 +/- 0.002 +/- 0.002 <br /> Tightness Test Results ® Pass ® Fail ® Pass 0 Fail F1 Pass ® Fail rl Pass ® Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results © Pass © Fail ® Pass © Fail ® Pass 0 Fail Pass Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />