Laserfiche WebLink
Buoyancy of Underground Tanks 6/22/2023 <br /> Fiberglass Straps with Deadman Anchors <br /> Deadman Deadman <br /> Deadman Anchor Guidelines Tank Diameter Width Height <br /> Notes: 48" 6" 6" <br /> Any size tank will require 2 deadmen,one each side of tank. 64" 12" 12" <br /> Each deadman shall lay parallel to tank shell and be located 84" 12" 12" <br /> so that no part of the deadman shall fall under any quadrant of 96" 12" 12" <br /> the tank. 114" 18" 12" <br /> Each deadman section shall have 2 anchor points 120" 18" 12" <br /> A separate attachment point shall be furnished for each strap. 126" 18" 12" <br /> If a single deadman is used between tanks,its width shall be 132" 24" 12" <br /> doubled in width. 144" 24" 12" <br /> All cable connections shall be tripled clamped. <br /> All holddown straps shall be uniformly tightened to tank surface. <br /> Deadman Anchors shall be adequately reinforced with rebar to prevent breaking. <br /> Disclaimer Statement: <br /> The attached information is supplied to you for information purposes only. <br /> Therefore,Modern Welding Company,their officers,directors nor subsidiaries there of accept any/no <br /> responsibility for the use of this information covered within.This information is advisory only and the use <br /> of the material and methods is solely at the risk of the user. <br /> e°F <br /> R. <br /> c� EXPIR38 z <br /> } 3- 4 Y <br /> p�k <br /> Fuel tanks must be <br /> installed with the specified <br /> dead men and straps <br /> 2 <br />