Laserfiche WebLink
Identification of Test Procedures for Secondary Containment Testing <br />To Whom It May Concern: <br />Tait Environmental Services, Inc., utilizes the following procedures when conducting Secondary <br />Containment Testing: <br />1)Containment Sumps, Transition Sumps, UDCs – Tait follows PEI RP1200 17 Section 6.6 for the <br />accelerated test method. Tait uses the Incon TS 1000 hydrostatic test equipment following the <br />attached procedures. <br />2)Spill Buckets; Direct Bury & Contained in Sumps – Spill buckets contained in sumps are tested <br />per PEI 1200 17, Section 6.2, however Tait Pass/Fail threshold is 0” drop in one hour. Direct Bury <br />Spill Buckets are test the same as containment sumps per PEI 1200 17, Section 6.6. <br />3)Tank Annular Space – testing is conducted per PEI 1200 17, Section 4.2 <br />4)Piping Secondary Containment – Testing is conducted per PEI RP1200 17, Section 5.3 <br />Please consider this letter as our Test Procedure utilized when conducting Secondary Containment <br />Testing in lieu of either parts or the whole RP1200 document due to copyright infringement.