Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2364956 Date: 2/5/2024 <br /> Site Name/ID: 7-ELEVEN#43254/4945/43254/4945 <br /> Address: 401 W KETTLEMAN LANE <br /> City: LODI State: CA Zip: 95240 <br /> Tank ID 1 2 <br /> Product REGULAR PREMIUM <br /> Product Line 1 1 <br /> Tested From 4 4 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. UNKNOWN UNKNOWN <br /> Pump Operating Pressure(psi) 30.00 38.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 30.00 38.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 80.00 100.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 20 26 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 3 4 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus S//aldivar Certification#: 115237 <br /> Technician Signature: /-1 14/- Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2024 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />