Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer 0 Industry Standard El Professional Engineer <br /> Test Type © Pressure 0 Vacuum E Hydrostatic <br /> Test Equipment Used: oMNTEC Proteus CLD <br /> Sump/UDC ID UDC 1-2 UDC 3-4 UDC 5-6 UDC 7-8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 9 9 9 9 <br /> Sump Bottom to Top of Bottom Bottom Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:23 12:23 12:23 12:23 <br /> Initial Reading 1.923 5.849 7.187 6.524 <br /> Test End Time 12:38 12:38 12:38 12:38 <br /> Final Reading 1.923 5.848 7.187 6.524 <br /> Change in Reading 0.000 0.001 0.000 0.000 <br /> Pass Fail Criteria +i-0.002 +i-0.002 +i- 0.002 +i- 0.002 <br /> Tightness Test Results El Pass rl Fail © Pass rl Fail © Pass © Fail © Pass El Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass Fail Criteria <br /> Tightness Test Results R7 Pass 0 Fail 0 Pass El Fail 0 Pass [rj Fail I! Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />