Laserfiche WebLink
SAN J O A Q U I ISIV I Environmental Health Department <br /> U IN 1 y <br /> . Gre�trless grows he, . . <br /> Underground Storage Tank Program Service Request Inspection Report <br /> Name of Facility: SPEEDWAY#4612 Date: 01/12/2024 <br /> Address: 2448 W KETTLEMAN LN , LODI 95242 <br /> Requestor: VERONICA FREITAS,WALTON ENGINEERING INC Telephone: (916)373-1166 <br /> Program Element: 2308-UST RETROFIT Request#: SR0087541 <br /> Inspection Type: 298-UST SERVICE REQUEST- FIELD ACTIVITY <br /> Onsite Service Technician: Anthony Reyes ICC Service Tech/Installer Exp. Date: 08/12/2024 <br /> Manufacturer training: FFS P1, 05/09/25 <br /> OVERALL INSPECTION NOTES AND COMMENTS <br /> NOTES <br /> On-site for 87 drop tube replacement with overfill shut-off valve. <br /> Verified 87 drop tube measured to 95%tank volume shut off. <br /> Verified tank charts were available for review at the time of inspection. <br /> Verified calculations at the time of inspection. <br /> Verified 87, 91 and diesel tanks had ball floats removed in 2019 overfill prevention inspection. <br /> Verified flapper functionality of drop tubes. <br /> Facility is approved to receive fuel in the 87 tank. <br /> The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br /> Safety Code.If a reinspection is required,fees will be assessed at the current hourly rate. <br /> Received by: Name and Title: Emailed to Veronica Freitas, <br /> EH Specialist: ALBERTO FERNANDEZ Phone: (209)616-3037 <br /> FA0003855 SR0087541 SC298 01/12/2024 <br /> EHD 23-01 Rev.07/05/2022 Page 1 of 1 Underground Storage Tank Program Service Request Inspection Report <br />