PRESSURE LINE LEAK SETUP <br />Q 1: 87-1 <br />PIPE TYPE: 2/3 inch Fiberglass <br />LINE LENGTH: 175 FEET <br />0.2 GAL/HR TEST: MONTHLY <br />0.1 GAL/HR TEST: AUTO <br />SHUTDOWN RATE: 3.0 GAL/HR <br />LOW PRESSURE SHUTOFF: ON <br />LOW PRESSURE: 10.0 psi <br />TANK: 1 - REGULAR <br />PRESSURE OFFSET: 0.0 psi <br />Q 2: 87-2 <br />PIPE TYPE: 2/3 inch Fiberglass <br />LINE LENGTH: 230 FEET <br />0.2 GAL/HR TEST: MONTHLY <br />0.1 GAL/HR TEST: AUTO <br />SHUTDOWN RATE: 3.0 GAL/HR <br />LOW PRESSURE SHUTOFF: ON <br />LOW PRESSURE: 10.0 psi <br />TANK: 1 - REGULAR <br />PRESSURE OFFSET: 0.0 psi <br />PIPE TYPE: 2/3 inch Fiberglass <br />LINE LENGTH: 300 FEET <br />0.2 GAL/HR TEST: MONTHLY <br />0.1 GAL/HR TEST: AUTO <br />SHUTDOWN RATE: 3.0 GAL/HR <br />LOW PRESSURE SHUTOFF: ON <br />LOW PRESSURE: 10.0 psi <br />TANK: 2 - PREMIUM <br />PRESSURE OFFSET: 0.0 psi <br />Q 4: DIESEL <br />PIPE TYPE: 2/3 inch Fiberglass <br />LINE LENGTH: 80 FEET <br />0.2 GAL/HR TEST: MONTHLY <br />0.1 GAL/HR TEST: AUTO <br />SHUTDOWN RATE: 3.0 GAL/HR <br />LOW PRESSURE SHUTOFF: ON <br />LOW PRESSURE: 10.0 psi <br />TANK: 3 - DIESEL <br />PRESSURE OFFSET: 0.0 psi <br />