SAN JOAQUIN <br />CCUNT <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />SAFEWAY FUEL CENTER #1769 <br />2802 COUNTRY CLUB BLVD, STOCKTON <br />April 04, 2024 <br />Single -Walled Non -Pressurized Piping <br />404 <br />CCR 2643(e), 2661(f) <br />Failure to conduct 0.1 gph test on single -walled gravity piping biennially or post repair (pre -1984) <br />❑ V ❑ R ❑ COS <br />Other Violations <br />2010 <br />See below <br />Unlisted General violation <br />❑ V ❑ R ❑ COS <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />117 <br />CCR 2637(e), 2637(f) Failed to submit "Secondary Containment Testing Report Form" within 30 days after the test. <br />OBSERVATION: Secondary containment testing was performed on 3/20/2023 A test report has not been submitted <br />to the EHD or the California Environmental Reporting System (CERS). <br />REGULATION GUIDANCE: A copy of the 'Secondary Containment Testing Report Form' must be submitted within <br />30 days of the test. <br />CORRECTIVE ACTION: Immediately provide this report to the EHD. <br />This is a repeat violation, Class II. <br />122 <br />CCR 2712(f) Failure to implement corrections and submit written response within 30 days of receiving the report. <br />OBSERVATION: An inspection was last done on July 25, 2023 and an inspection report was issued identifying <br />information to be submitted to bring this site into compliance. This information was required to be submitted by <br />August 25, 2024. This information was not received but was observed on site in the facility's binder. <br />REGULATION GUIDANCE: An operator that receives an inspection report shall have 30 days to implement the <br />corrections specified in the inspection report and comply with permit conditions. The corrective action shall include <br />all of the recommendations made in the report. The operator shall submit a written response that includes a <br />statement documenting corrective actions taken or proposing corrective actions which will be taken. <br />CORRECTIVE ACTION: Ensure that a written response documenting corrective actions taken or proposed is <br />submitted and all corrections implemented within 30 days of receiving an inspection report. <br />This is a repeat violation, Class II. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by May 4, 2024 . <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in -office CERS help will be provided at EHD hourly rate <br />($162). To schedule an appointment, please call (209) 468-3420. <br />FA0012764 PR0516736 SCO01 04/04/2024 <br />EHD 23-01 Rev. 12/06/2021 Page 4 of 5 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />