Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> 91 East&91 West Secondary Piping Failed Due to Inability to Secure Test Boots Over Secondary Line. Secondary Lines <br /> Need to be Cut Back from Primary&Torn Product Penetration Boot to 91 Piping. <br /> 87&91 STP Sumps Failed Due to Torn Product Penetration Boots. <br /> Diesel Fill Sump Increased.Adjust/Compensate for Increase. Block for Wind; Eliminate Potential Vibrations; Adjust for <br /> Traffic; Adjust for Testing Probe -Retested and Passed. <br /> UDC 15/16 Failed Due to torn 91 Product Test Boot. <br /> UDC 7/8 Increased.Adjust/Compensate for Increase. Block for Wind; Eliminate Potential Vibrations;Adjust for Traffic; <br /> Adjust for Testing Probe-Retested and Passed. <br /> No Inspector Present. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5of5 <br />