Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />8. SUMP/UDC TEST <br />Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br />Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br />Test Equipment Used: Incon hydrostatic tester <br />Sump/UDC ID <br />87 STP <br />91 STP <br />Diesel STP <br />Sump Manufacturer <br />Bravo <br />Bravo <br />Bravo <br />Sump Depth (inches) <br />61" <br />60.75" <br />61.6125" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />14" <br />16" <br />16" <br />Test Start Time <br />10:21 am <br />10:21 am <br />10:21 am <br />Initial Reading <br />2.3818 <br />2.2379 <br />2.6568 <br />Test End Time <br />10:36 am <br />10:36 am <br />10:36 am <br />Final Reading <br />2.3817 <br />2.2382 <br />2.6565 <br />Change in Reading <br />0.0001 <br />-0.0003 <br />0.0003 <br />Pass/Fail Criteria <br />0.0020 <br />0.0020 <br />0.0020 <br />Tightness Test Results <br />p Pass ❑ Fail <br />0 Pass ❑ Fail <br />0 Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Sump/UDC ID <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass ail Criteria <br />Tightness Test Results <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Additional copies of this page may be attached. <br />All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />