Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ❑x Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ❑x Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID UDC 9&10 UDC 11&12 UDC 11-S UDC 12-S&13 <br /> Sump Manufacturer Western FG Bravo Bravo Bravo <br /> Sump Depth (inches) 31" VPH EXEMPT VPH EXEMPT VPH EXEMPT <br /> Sump Bottom to Top of 21" VPH EXEMPT VPH EXEMPT VPH EXEMPT <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:52 VPH EXEMPT VPH EXEMPT VPH EXEMPT <br /> Initial Reading .001 VPH EXEMPT VPH EXEMPT VPH EXEMPT <br /> Test End Time 9:22 VPH EXEMPT VPH EXEMPT VPH EXEMPT <br /> Final Reading .001 VPH EXEMPT VPH EXEMPT VPH EXEMPT <br /> Change in Reading 0 NA NA NA <br /> Pasnesss/Fail Criteria > .002 NA NA NA <br /> TightTest Results © Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 13-S&14 <br /> Sump Manufacturer Bravo <br /> Sump Depth (inches) VPH EXEMPT <br /> Sump Bottom to Top of VPH EXEMPT <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time VPH EXEMPT <br /> Initial Reading VPH EXEMPT <br /> Test End Time VPH EXEMPT <br /> Final Reading VPH EXEMPT <br /> Change in Reading NA <br /> Pass/Fail Criteria NA <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4of5 <br />