CAGASOLINE AGS 2115 W. Yosemite Ave Manteca Ca <br /> Received <br /> Violation 301/315/327 4/23/2024 <br /> The Fluid in the vent sump was found to be murky <br /> Corrective Action: <br /> Drained reservoir of Dirty Brine and added new Western Fiberglass Brine as required. No <br /> signs of leaks were observed in the transition sump. Tested continuity all ok. <br /> Violation 304 <br /> Large amount of oily liquid was observed in UDC 5/6 and 11/12 <br /> Corrective action: <br /> Removed liquid and tested with water finding paste to determine if this was fuel or product. <br /> Liquid was found to be water. Cleaned all liquid and inspected udc's for any signs of leaks. <br /> None found. Checked all UDC's while on site for any signs of leaks or water intrusion. Found <br /> none. <br /> Violation 305 <br /> Approximately two cups of brine was found in the 91 STP sump indicating a leak in the <br /> secondary containment. <br /> Corrective Action: <br /> Cleaned all liquid from 91 STP sump and inspected all penetration fittings. No leaks were <br /> present at this time. Techs determined the brine was not from the reservoir due to location of <br /> brine in the sump. Techs cleaned all sump walls with simple green and acetone to remove <br /> any stains on sump walls. Sump is being monitored to see if leaks start again from any <br /> penetration fittings. We will be able to see the leak by the runoff of brine down the sump walls. <br /> We are going to return on 4/25 and check the 91 STP sump. If liquid is found at this time we <br /> will determine where the leak is coming from. If leak is not visible we will need to drain brine <br /> and test sump to find the leak. After testing we will determine scope of work and pull permits <br /> to make corrections at that time. We will update the site owner and EHD of the findings at that <br /> time. Checked all other fill and STP sumps at this time and no signs of liquid was observed in <br /> any of the other sumps at this location <br />