Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> i , �V <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AHMEDS SONS INC 1257 W YOSEMITE AVE, MANTECA April 01, 2024 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e) Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the 87, 91, and diesel fill sumps.A hand pump was able to be located by <br /> employee on site but no hose attachment was able to be found by facility employee. Service technician removed <br /> liquid at the time of the inspection. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed greater than 1 gallon of liquid from the 87, 91, and diesel <br /> fill sumps. Ensure a means of removing water from secondary containment is available for removal of water. <br /> Provide supporting documents to the EHD. <br /> This is a repeat violation, Class II. <br /> 318 CCR 2635, 2637.1,2665, 2712 Failed to meet spill container requirements. <br /> OBSERVATION: The diesel and 87 tank spill containers failed to have a minimum capacity of five gallons. <br /> REGULATION GUIDANCE:All spill containers shall have a minimum capacity of five gallons. <br /> CORRECTIVE ACTION: Technician replaced spill container gaskets at the time of inspection, and was able confirm <br /> 5-gallon capacity and re-test. Ensure EHD notification made and on-site paperwork is maintained per the EHD UST <br /> service request guidance. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of inspection. A complete report was <br /> finished on 4/29/2024 and replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report, 5/29/2024. <br /> **TESTING IS INCOMPLETE**The 87, 91, and Diesel annular sensors have not been tested. Service <br /> technician was unable to remove and test the sensors according to manufacturer guidelines at the time of <br /> inspection without reportedly damaging the sensors. Technician plans to complete testing at a later date. The <br /> 87, 91, and Diesel annular sensors are due for testing by 4/30/24. Immediately schedule this test and provide 48 <br /> hours notification to the EHD. All EHD staff time associated with the reinspection will be billed at the current <br /> hourly rate ($162). <br /> FA0003707 PR0231463 SCO01 04/01/2024 <br /> EHD 23-01 Rev.12/06/2021 Page 9 of 10 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />