Laserfiche WebLink
SAN 10AQUIN Environmental Health Department <br /> C. .)1,J Pv I Y <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> 7-ELEVEN INC#32190 4943 S HWY 99 , STOCKTON April 17 2024 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> rItem# Remarks <br /> 302 CCR 2630(d), 2641(a) Leak detection equipment not installed/maintained/located to detect leaks at earliest <br /> opportunity. <br /> OBSERVATION: Hoses attached to the boots were looped upward and not positioned in a way that leaks will be <br /> detected at the earliest opportunity. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed, trained, and certified contractor to ensure that any <br /> releases in the piping in the UDCs will be detected at the earliest opportunity. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 4/17/24, 30 days from now. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($162). To schedule an appointment, please call (209)468-3420. <br /> ****MONITORING SYSTEM CERTIFICATION IS INCOMPLETE. THE DIESEL LEAK DETECTOR WAS NOT <br /> TESTED AT TIME OF INSPECTION*** <br /> ***TESTING OF DIESEL LEAK DETECTOR IS DUE BY 4/30/2024. PROVIDE 48 HOURS OF WRITTEN <br /> NOTIFICATION TO EHD*** <br /> ALL EHD STAFF TIME ASSOCIATED WITH THE RE-INSPECTION WILL BE BILLED AT THE CURRENT <br /> HOURLY RATE($162) <br /> AFTER THE COMPLIANCE DATE,EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: April 17, 2024 Inspector: Inspector Phone: <br /> Printed Name and Title: MARIA LOPEZ, EHS Trainee (209)616-3064 <br /> Emailed to Nima Badial, Owner <br /> FA0007458 PR0506488 SCO01 04/17/2024 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />