Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by 0 Manufacturer 0 Industry Standard El Professional Engineer <br /> Test Type © Pressure El Vacuum E Hydrostatic <br /> Test Equipment Used: OMNTEC Proteus CLD Series <br /> Sump/UDC ID 87 STP 91 STP UDC 1-2 UDC 3-4 <br /> Sump Manufacturer Xerxes Xerxes Bravo Bravo <br /> Sump Depth (inches) 52 54 9 9 <br /> Sump Bottom to Top of 20 20 Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 15:36 09:46 09:46 09:46 <br /> Initial Reading 6.592 9.389 5.196 6.080 <br /> Test End Time 15:51 09:46 09:46 09:46 <br /> Final Reading 5.592 9.389 5.196 6.080 <br /> Change in Reading 0.0000 0.0000 0.0000 0.0000 <br /> Pass Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results F1 Pass rl Fail F1 Pass r] Fail El Pass 0 Fail © Pass Ej Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results R7 Pass 0 Fail 0 Pass El Fail © Pass [rj Fail M Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />