Laserfiche WebLink
JONES COVEY GROUP, INC. <br />COMPLETE FUEL SYSTEM CONSTRUCTION fx MAINTENANCE SERVICES <br />MECHANICAL/ ELECTRONIC LEAK DETECTOR CERTIFICATION <br />SITE: Pilot Flying J 618 Ripon <br />State Facility # <br />618 <br />DATE: <br />CONTACT <br />PHONE: <br />JOB #: <br />11/01/2024 <br />Site Manager - Amy <br />(888) 972-7875 <br />2486185-1-2 <br />Tank # <br />Tank 3 <br />Product <br />Diesel <br />LD Manufacturer <br />VMI <br />LD Model <br />99 LD -2000E <br />Sump Condition <br />Good <br />Operation Pressure <br />35 Psi <br />PSI <br />Opening Time (Sec) <br />18 Sec <br />Metering Pressure <br />23 Psi <br />(PSI) <br />Functional Element <br />33 Psi <br />Holding Pressure <br />Leak Rate LD Detected <br />3.00 GPH <br />(GPH) <br />Does LD Detect 3 GPH <br />Yes <br />Leak Rate? <br />LD Serial <br />71925 <br />Comments: <br />Technician Shawn Rodriguez <br />Signature <br />License Number VMI #4822 <br />9595 LUCAS RANCH ROAD, RANCHO CUCAMONGA, CA 91730 - LICENSED IN 41 STATES <br />California State License #804431 A, B, HAZ <br />