Laserfiche WebLink
TABLE 9 <br /> Scope and Frequency of AST Container Inspections and Tests <br /> T & T TRUCKING, INC. <br /> 11396 North Highway 99, Lodi, California <br /> Tank ID <br /> Inspection/Test Diesel ASTs Oil ASTs Gasoline Waste Oil <br /> (Fixed) (Fixed) AST AST Oil Drums <br /> Visual inspection by Facility Monthly Monthly Monthly Monthly <br /> personnel (as per checklist of Annual Annual Annual Annual Daily <br /> Appendix C) <br /> External inspection by certified Per STI Per STI Per STI Per STI <br /> inspector(as per STI Standard Standard — Standard — Standard — Standard — <br /> SP-001) 20 years 20 years 20 years 5 years <br /> Internal inspection by certified <br /> inspector(as per STI Standard t t t t <br /> SP-001) <br /> Tank tightness test meeting 5 years <br /> requirements of 40 CFR 280 <br /> Notes:The frequency above is based on implementation of a scheduled inspection/testing program.To initiate the program,ASTs will <br /> be inspected by the following dates: <br /> AST Implementation of Testing Date <br /> Following shell repairs or as directed by local enforcement agency—the <br /> Diesel Fuel AST last integrity testing was done in December 2018. The next planned <br /> testing date is recommended for 2038. <br /> Legend: AST:aboveground storage tank <br /> STI:Steel Tank Institute <br /> SP 001:standard and number designation <br /> M:Monthly <br /> A:Annual <br /> ':Or earlier,as recommended by the certified inspector based on findings from an external inspection. <br /> t: Internal inspection may be recommended by the certified inspector based on findings from the external inspection. <br /> CFR:code of federal regulations <br />