Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> SOHAL#3 1 2494 E FREMONT ST STOCKTON May 22 2024 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement D OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 47 CA Health and Safety Code 25290.1(c3), 25290.2(c3)2030008-Secondary containment installed after July 1, 2003 is <br /> free of water. <br /> OBSERVATION:Water was found in the 87 and 91 fill sumps <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: Immediately remove this liquid, make a hazardous waste determination per Title 22 hazardous <br /> waste regulations, and manage accordingly. Immediately contact a properly licensed, trained, and certified contractor <br /> to address the water intrusion into the 87 and 91 sump under permit and inspection of the EHD, if needed. <br /> This is a repeat violation (Class 2) Violation. <br /> 77 CA Code of Regulations 2712(f)2030073- Facility has corrected cited violations within 30 days of receiving report. <br /> OBSERVATION:An inspection was last done on 5/22/2023 and an inspection report was issued identifying information <br /> to be submitted to bring this site into compliance. This information was required to be submitted by 6/21/2023 .This <br /> information has not been received resulting in a non-compliant status for this facility. <br /> REGULATION GUIDANCE:An operator that receives an inspection report shall have 30 days to submit a written <br /> response that includes a statement documenting corrective actions taken or proposing corrective actions which will be <br /> taken. <br /> CORRECTIVE ACTION: Ensure that a written response documenting corrective actions taken or proposed is <br /> submitted within 30 days of receiving an inspection report. <br /> Open violations form 2023: <br /> (1) Failure to implement corrections and submit written response within 30 days of receiving the report <br /> (2) Failure to comply with the designated operator inspection requirements <br /> This is a repeat violation (Class 2) Violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 6/21/2024. <br /> FA0003863 PR0231104 SCO01 05/22/2024 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />