Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID UDC 9&10 UDC 11&12 <br /> Sump Manufacturer CSI CSI <br /> Sump Depth (inches) 29 1/2" 29" <br /> Sump Bottom to Top of 14" 13 1/2" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:37 12:42 <br /> Initial Reading .001 .001 <br /> Test End Time 1:07 1:12 <br /> Final Reading .001 .001 <br /> Change in Reading 0 0 <br /> Pass/Fail Criteria > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID 1-87-FS 2-91-FS 3-Dsl-FS <br /> Sump Manufacturer XERXES XERXES XERXES <br /> Sump Depth (inches) 65" 70" 62 1/2" <br /> Sump Bottom to Top of No Piping No Piping No Piping <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:47 10:27 11:07 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 10:17 10:57 11:37 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />