Laserfiche WebLink
Triangle LT-3 Line Test Results Sheet SA-45798 <br /> Site: Lodi CA FO Term (Intl) Date: 2024-05-30 <br /> 2500 W Turner Rd <br /> Lodi, CA 95242 <br /> Line Start End Change Leak Test <br /> Product Test Volume COE Time Level Temp Time Level Temp Time Level Temp Rate Result <br /> # gals. hh:mm ml Degrees F hh:mm ml Degrees F Minutes ml Degrees F GPH Pass/Fail <br /> Diesel 1 11:08 200 11:23 199 15 0.01 0.01 Pass <br /> 2 <br /> 3 <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> 9 <br /> 10 <br /> 11 <br /> 12 <br /> 13 <br /> 14 <br /> 15 <br /> 16 <br /> I certify the above tests were conducted on this date,according to the Triangle's procedures and limitations and the results as listed are to <br /> my knowledge true and correct. <br /> License#: #1773 Results: <br /> Technician: Jamel Hamdan CFR=Corrected Final Result(gph). <br /> LC=Level Change(ml)in fifteen minutes. <br /> Signature: " ' __ TC=Temperature change(F)in fifteen minutes. <br /> V=Volume of line in <br /> COE=Coefficient of thermal expansion(gasoline 0.0007 g/degree F), (diesel 0.00045 g/degree F) <br /> Revised 3/29/2014, MRL <br />