Laserfiche WebLink
Program Element: 2303 - UST/PIPING INSTALLATION <br />Telephone: (510) 333 7802 Requestor: SUNNY GHAI, WINTER GATEWAY INC <br />Inspection Type: 333 - INSPECTION/REINSPECTION (Chargeable) <br />Address: 630 E ELEVENTH ST , TRACY 95304 <br />Date: 07/25/2024Name of Facility: DOWNTOWN TRACY SERVICE STATION <br /> Service Request Inspection Report <br />Request #: SR0086956 <br />Environmental Health Department <br />Onsite Service Technician: Tyler Swengel <br />Manufacturer training: NOV, 09/14/24 <br />ICC Service Tech/Installer Exp. Date: 11/29/2024 <br />OVERALL INSPECTION NOTES AND COMMENTS <br />NOTES <br />Witnessed reinspection of primary piping and pressure test prior to backfill : Soap test of all piping joints and penetrations <br />(product, vapor recovery and vent), and pressure test of 87 product @ 51 psi, diesel product @51 psi, Vapor recovery @ 41 psi, <br />91 product @ 51 psi, 87 vent @ 42 psi, 91 vent @42 psi, and diesel vent @42 psi. <br />All passed. <br />Note: Refer to approval letter dated June 5, 2024 for additional testing. <br />The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br />Safety Code. If a reinspection is required, fees will be assessed at the current hourly rate. <br />Received by: Name and Title: <br />EH Specialist:Phone:(209) 616-3049 <br />, <br />PAUL NSO <br />Sunny Ghai, Project Contact <br />Page 1 of 1EHD Rev. 09/16/2020 Service Request Inspection Report <br /> SR0086956 SC333 07/25/2024