Laserfiche WebLink
hps://www.epa.gov/sites/default/files/2015-12/documents/minrisk-acve-ingredients-tolerances-2015-12- <br />15.pdf <br /> <br />It ’s when there is oil added for applicaon purposes that the Oil Polluon Prevenon regulaons may be <br />applicable. Containers storing oil to be added would be regulated under SPCC prior to mixing (if containers are <br />55-gal capacity or greater and the total facility storage capacity exceeds 1,320 gallons). If the oil is mixed with <br />pescide and that mixture is stored rather than applied, that storage containers is regulated (again, the 55 and <br />1,320 gallon capacies apply) – as the quote in your email also states. <br /> <br /> <br />Would be glad to talk, if this has caused more confusion. <br />  <br />Janice <br /> <br />Janice Witul <br />US EPA R9 Oil Program <br />75 Hawthorne St., ECAD-3-2 <br />San Francisco CA 94105 <br />415 972 3089 <br /> <br />From: Reich, Peter <Reich.Peter@epa.gov> <br />Sent: Thursday, August 10, 2023 11:12 AM <br />To: Eddie Phillips <Eddie.Phillips@wilburellis.com>