Laserfiche WebLink
Environmental Health Department <br />Aboveground Petroleum Storage Act Inspection Report <br />Date: <br />June 04, 2024 <br /> Facility Address: <br /> 13771 Prescott Rd, Manteca <br /> Facility Name: <br /> Wilbur-Ellis Company LLC: Manteca <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 610 CFR 112.7(a)(3vi), 112.7(a4) Plan failed to adequately detail information and procedures for reporting a discharge. <br />OBSERVATION: The Spill Prevention, Control, and Countermeasure (SPCC) Plan information and procedures for <br />reporting a discharge are not included within the Plan. A contact list and phone numbers for the facility response <br />coordinator and CalOES which must be contacted in case of a discharge must be included within the Plan. <br />Information and procedures that would enable a person reporting an oil discharge to relate all information, as <br />described in 40 CFR 112.7(a)(4), unless facility submitted a Facility Response Plan. <br />REGULATION GUIDANCE: The SPCC plan shall include: (vi) Contact list and phone numbers for the facility <br />response coordinator, National Response Center, cleanup contractors with whom you have an agreement for <br />response, and all appropriate Federal, State, and local agencies who must be contacted in case of a discharge as <br />described in § 112.1(b). <br />(4) Unless you have submitted a response plan under § 112.20, provide information and procedures in your Plan to <br />enable a person reporting a discharge as described in § 112.1(b) to relate information on the exact address or <br />location and phone number of the facility; the date and time of the discharge, the type of material discharged; <br />estimates of the total quantity discharged; estimates of the quantity discharged as described in § 112.1(b); the <br />source of the discharge; a description of all affected media; the cause of the discharge; any damages or injuries <br />caused by the discharge; actions being used to stop, remove, and mitigate the effects of the discharge; whether an <br />evacuation may be needed; and, the names of individuals and/or organizations who have also been contacted. <br /> <br />CORRECTIVE ACTION: Immediately amend the SPCC Plan to include the current facility response coordinator, <br />CalOES phone number, and procedures for reporting a discharge somewhere that is easily accessible. Submit <br />proof of correction to the EHD. <br />This is a repeat violation, Class II. <br />FA0010178 PR0515663 SC001 06/04/2024 <br />EHD 28-01 Rev. 12/06/2021 Aboveground Petroleum Storage Act OIRPage 7 of 10 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD