Laserfiche WebLink
Environmental Health Department <br />Aboveground Petroleum Storage Act Inspection Report <br />Date: <br />June 04, 2024 <br /> Facility Address: <br /> 13771 Prescott Rd, Manteca <br /> Facility Name: <br /> Wilbur-Ellis Company LLC: Manteca <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 712 CFR 112.7(e), 112.8(c)(6) Failed to perform scheduled tank tests or inspections by appropriately qualified <br />personnel. <br />OBSERVATION: Facility failed to ensure that tanks are inspected and tested by an appropriately qualified person in <br />accordance with industry standards. The TI-3386, Fire Pump Tank, Waste Oil Tank #1, Waste Oil Tank #2, <br />Gasoline Tank, Motor Oil Tank #1, Motor Oil Tank #2, and Hydraulic Oil Tank were not tested/inspected on <br />schedule. The schedule per the SPCC Plan is annually and monthly with records for the past three years. <br />REGULATION GUIDANCE: 112.8(c)(6) Test or inspect each aboveground container for integrity on a regular <br />schedule and whenever you make material repairs. You must determine, in accordance with industry standards, the <br />appropriate qualifications for personnel performing tests and inspections, the frequency and type of testing and <br />inspections, which take into account container size, configuration, and design (such as containers that are: <br />shop-built, field-erected, skid-mounted, elevated, equipped with a liner, double-walled, or partially buried). Examples <br />of these integrity tests include, but are not limited to: visual inspection, hydrostatic testing, radiographic testing, <br />ultrasonic testing, acoustic emissions testing, or other systems of non-destructive testing. You must keep <br />comparison records and you must also inspect the container's supports and foundations. In addition, you must <br />frequently inspect the outside of the container for signs of deterioration, discharges, or accumulation of oil inside <br />diked areas. Records of inspections and tests kept under usual and customary business practices satisfy the <br />recordkeeping requirements of this paragraph. <br />112.7(e) Inspections, tests, and records. Conduct inspections and tests required by this part in accordance with <br />written procedures that you or the certifying engineer develop for the facility. You must keep these written <br />procedures and a record of the inspections and tests, signed by the appropriate supervisor or inspector, with the <br />SPCC Plan for a period of three years. Records of inspections and tests kept under usual and customary business <br />practices will suffice for purposes of this paragraph. <br />CORRECTIVE ACTION: Ensure that all tanks are inspected and tested by an appropriately qualified person in <br />accordance with industry standards and records are kept for the past three years. Submit a statement ensuring all <br />tanks will be inspected and tested appropriately to the EHD. <br />This is a repeat violation, Class II. <br /> 724 CFR 112.8(d)(4) Failed to regularly inspect aboveground valves, piping, and appurtenances. <br />OBSERVATION: The facility failed to regularly inspect aboveground valves, piping, and appurtenances. Per <br />manager and onsite records, inspections were not being conducted for some time prior to 2023. <br />REGULATION GUIDANCE: (d)(4) Regularly inspect all aboveground valves, piping, and appurtenances. During the <br />inspection, you must assess the general condition of items, such as flange joints, expansion joints, valve glands and <br />bodies, catch pans, pipeline supports, locking of valves, and metal surfaces. <br />CORRECTIVE ACTION: Immediately inspect all aboveground valves, piping, and appurtenances and ensure <br />inspections are done regularly. Provide a statement of compliance going forward to the EHD. <br />This is a Class II violation. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />FA0010178 PR0515663 SC001 06/04/2024 <br />EHD 28-01 Rev. 12/06/2021 Aboveground Petroleum Storage Act OIRPage 9 of 10 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD