Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Manteca Valero 1 1700 E YOSEMITE AVE MANTECA August 13 2024 <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 7 CA Code of Regulations 2715(a)(1)(B), 2715(a)(3)2010003-Owner/Operator submitted DO form and/or informed the <br /> CUPA of any change(s)within 30 days(TCR 10). <br /> OBSERVATION:A new designated operator, Renee Eastwood, began conducting inspections in July 2024 and <br /> notification was not provided to the EHD within 30 days of the change. <br /> REGULATION GUIDANCE:The owner or operator shall submit a"Designated Underground Storage Tank Operator <br /> Identification Form" no later than 30 days after any change in the designated UST operator(s). <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> http://cers.calepa.ca.gov and upload the notification identifying all the designated operators for this facility. <br /> This is(Minor)Violation. <br /> 28 CA Code of Regulations 2638(a),26410)2030043- Leak detection equipment properly installed, calibrated,operated, <br /> and maintained (TCR 9d). <br /> OBSERVATION:The mechanical leak detector(LD2000)failed when test was conducted, service technician replaced <br /> like for like leak detector.After replacement, leak detector passed test. <br /> REGULATION GUIDANCE:All monitoring equipment shall be installed, calibrated, operated, and maintained in <br /> accordance with manufacturer's instructions, and certified for operability, proper operating condition, and proper <br /> calibration. Immediately contact a properly licensed and certified contractor to [NOTE FIX NEEDED]. <br /> CORRECTIVE ACTION: The mechanical leak detector(LD2000)was replaced and now functions properly. <br /> This violation was Corrected On Site <br /> This is (Class 2)Violation. <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12). <br /> 1.)OBSERVATION: The designated operator inspections for the following months were performed more than 30 days <br /> after the previous inspection: <br /> - Initial inspection on 12/6/2023, next inspection performed on 1/30/2024 <br /> (55 days) <br /> REGULATION GUIDANCE:The designated operator visual inspections shall be conducted within 30 days or less of <br /> the previous inspection. <br /> CORRECTIVE ACTION: Ensure that all designated operator inspections are performed within the required time frames. <br /> FA0003796 PR0231454 SCO01 08/13/2024 <br /> EHD Rev.12/06/2021 Page 5 of 7 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />