Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-WO-PS 2-WO-PS 3-Anit Frez 4-Gear Oil <br /> Sump Manufacturer CSI CSI CSI CSI <br /> Sump Depth (inches) 44" 115" 65" 65" <br /> Sump Bottom to Top of 16" 24" 27" 27" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:17 11:37 10:47 10:52 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 11:47 12:07 11:17 11:22 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Ess/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID 5-Motor O-PS 6-Waste O-PS 7-Soap-PS <br /> Sump Manufacturer CSI CSI CSI <br /> Sump Depth (inches) 65" 74" 47" <br /> Sump Bottom to Top of 27" 16" 22" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:57 11:02 10:37 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 11:27 11:32 11:07 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />