A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> TRACY USD-SERVICE CENTER 1 1975 W LOWELL AVE TRACY January 23 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 5 CA Code of Regulations 2632(d),2641(h)2030041 -A current facility plot plan is maintained and has been submitted. <br /> OBSERVATION:An accurate UST Monitoring Site Plan was not submitted.The site map in CERS does not indicate <br /> location of annular sensors for diesel and 87 tank. <br /> REGULATION GUIDANCE:A site plan must be submitted identifying the locations where monitoring will be performed. <br /> The site plan must show the general layout of tanks and clearly identify locations of the following equipment, if <br /> installed: 1) monitoring panels; 2)in-tank liquid level probes(if used for leak detection); 3)devices monitoring tank <br /> annular spaces or vault;4)devices monitoring product piping; 5)devices monitoring fill piping; 6)devices monitoring <br /> vent piping; 7)devices monitoring vapor recovery piping; 8)devices monitoring vent/transition sumps; 9)devices <br /> monitoring under-dispenser containment; 10)line leak detectors; and 11)devices monitoring any other secondary <br /> containment areas. <br /> CORRECTIVE ACTION: This was corrected on site. A site map indicating location of annular sensors were uploaded <br /> to CERS during the inspection. <br /> This is a repeat violation (Class 2) Violation. <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12). <br /> OBSERVATION:The designated operator failed to check and note the correct test dates for the Overfill Prevention <br /> Equipment testing on the designated operator inspection reports from 2/14/2024 through 7/3/2024.The incorrect date <br /> written was 9/27/2021.The correct date for the Overfill Prevention Equipment testing during that timeframe was <br /> 1/19/2024. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of the <br /> required information on the reports. <br /> This is a repeat violation (Class 2) Violation. <br /> Overall Inspection Comments: <br /> Routine UST Inspection <br /> FA0004044 PR0232521 SCO01 01/23/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />