Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPIUDC TEST <br /> Test Method Developed by ❑ Manufacturer 13 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum i❑ Hydrostatic <br /> Test Equipment Used: <br /> Sump1UDC ID #112 UDC #314 UDC #516 UDC #718 UDC <br /> Sump Manufacturer Ameron Ameron Ameron Ameron <br /> Sump Depth (inches) 23" 23" 23" 23 <br /> 11 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> 14" 14" 14" 14" <br /> (inches) <br /> Test Start Time 0 mins 0 mins 0 mins 0 mins <br /> Initial Reading 0 0 0 0 <br /> Test End Time 30 mins 30 mins 30 mins 30 mins <br /> Final Reading 0 0 0 0 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria pass Pass Pass Pass <br /> Tightness Test Results 13 Pass ❑ Fail 0 Pass ❑ Fail 12 Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID #9f10 UDC #11112 UDC 87 STP Sum <br /> Sump Manufacturer Ameron Ameron Total Containment <br /> Sump Depth (inches) 23" 2Y „ <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 14" 14" 23" <br /> (inches) <br /> Test Start Time 0 mins 0 mins 0 mins <br /> Initial Reading 0 0 0 <br /> Test End Time 30 mins 30 mins 30 mins <br /> Final Reading 0 0 0 <br /> Change in Reading 0 0 0 <br /> Pass ail Criteria Pass Pass <br /> Tightness Test Results 13 Pass ❑ Fail 2 Pass ❑ Fail ❑ Pass ❑ Fail ® Pass ❑ Faill, <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />