Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Yosemite Avenue Arco AmPm 1 1711 E Yosemite AVE Manteca March 13 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 45 CA Code of Regulations 2636(f)(2)2030025-LLD on DW press piping monitors hrly, detects a 3.0 gph leak, and <br /> restricts/shuts off flow(TCR 9d). <br /> OBSERVATION:The 91 VMI line leak detector(99-LD2000)failed to detect a leak when tested. <br /> REGULATION GUIDANCE:All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: The service technician adjusted the leak detector, retested it, and it passed. <br /> This is a repeat violation (Class 2) Violation. <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12). <br /> OBSERVATION:The designated operator failed to check and note the correct test dates for the overfill testing on the <br /> designated operator inspection reports.The following DO reports had the incorrect overfill test date documented: 3/27, <br /> 4/24, 5/22, 6/19, 7/17, 8/14, 9/11, 10/9, and 11/6. The correct date for the Overfill testing is 3/25/24. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of the <br /> required information on the reports. <br /> This is a repeat violation (Class 2) Violation. <br /> Overall Inspection Comments: <br /> Routine Monitoring System Certification <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by April 12, 2025. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead of <br /> having them sign. <br /> FA0003612 PR0231455 SCO01 03/13/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />