<br />2.0 Secondary Containment <br />Observations Comments/Recommendations <br />Secondary Containment Type Containment Dike <br />Secondary Containment Length 43' <br />Secondary Containment Width 19' <br />Secondary Containment Height 4' <br />Secondary Containment Volume (gallons)24,446 Containment area is able to hold 110% of the tank. <br />Secondary Containment Condition <br />(breaches, foreign material, liquid)Fair 1 inch of standing water. ** <br />Secondary Containment Drain Valve <br />Installed?No Drain valve with lock should be installed on secondary <br />containment wall. ** <br />Drain Valve Locked?N/A <br />Sump Pump Installed?No <br />Is The Sump Pump Float or Manually <br />Activated?N/A <br />Other <br /> <br />3.0 Secondary Containment (AST) <br />Observations Comments/Recommendations <br />Secondary Containment (AST) - D/W, Double <br />Bottom or Secondary Containment (Pans, <br />Boxes or Containers) <br />N/A <br />AST Containment Condition? Dry?N/A <br />Drain Valve Installed N/A <br />Drain Valve Locked?N/A <br />Other <br /> <br />4.0 Tank Appurtenances <br />Piping Observations Comments/Recommendations <br />Ancillary Equipment: Piping / Piping <br />Connections (leaks, corrosion, supports)Good <br />Other <br />Valves Observations Comments/Recommendations <br />Anti Siphon Valve installed?Yes <br />Anti Siphon Valve Manufacturer Solenoid Valve Tank appears to have a solenoid valve installed. <br />Anti Siphon Valve Model Unknown <br />Is the Anti Siphon Valve Operational And <br />Properly Sized?Yes <br />Fire Valve Installed?N/A <br />Fire Valve Manufacturer N/A <br />Fire Valve Model Number N/A <br />Is the Fire Valve Operational?N/A <br />Other <br />Vents Observations Comments/Recommendations <br />Normal Vent Manufacturer Unknown <br />Normal Vent Size 2" <br />Normal Vent Model Unknown <br />Normal Vent Condition Fair Vent is greasy and dirty. ** <br />Normal Vent Properly Sized?No <br />Per NFPA 30 section 21.4.3 the normal vent shall be at <br />least as large as the largest filling or withdrawal <br />connection. ** <br />4