Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> -�wTanknology Line Leak Detector Test <br /> Work Order: 2379618 Date: 5/1/2025 <br /> Site Name/ID. Rebel Store#0375/0375 <br /> Address: 2375 W Grant Line Road <br /> City: Tracy State: CA Zip: 95377 <br /> Tank ID REGULAR 87 REGULAR AUX PREMIUM 91 DIESEL <br /> Product REGULAR REGULAR PREMIUM Biodiesel <br /> Product Line 1 1 1 1 <br /> Tested From 2 2 18 16 <br /> Existing/New Existing Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> Serial No. U.R. U.R. U.R. U.R. <br /> Pump Operating Pressure(psi) 40.00 30.00 30.00 36.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 3.00 <br /> Holding PSI <br /> N/A for Electronic Lo's <br /> Resiliency(ml) <br /> N/A for Electronic Lo's <br /> Metering PSI <br /> N/A for Electronic LD's <br /> Opening Time(sec) <br /> N/A for Electronic LD's <br /> Test Results Pass Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> r <br /> Technician Signature: f. Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />