Laserfiche WebLink
PEI/RP1200-12 <br /> 4.2.4 Preparation. The procedures in this sec- 4.2.7 Test Equipment. Test equipment shall <br /> tion are general in nature and reflect the suggested include: <br /> vacuum levels and hold times for testing tank a vacuum-generating device that can be used in <br /> secondary contaimnent auras. Consult tank manu- a Glass I,Division 1 area capable of pulling 15 <br /> facturer and authority having jurisdiction (AHJ) inches of mercury(Hg) vacuum; <br /> guidelines before performing these tests as their <br /> requirements may differ. an automatic vacuum shutoff valve or vacuum <br /> regulator(The shutoff valve can be set to close at <br /> Determine if there is liquid present in the intersti- a predetermined safe level,preventing the pos- <br /> tial space. If liquid is found,determine if the fluid <br /> is water or product, and remove it to the extent <br /> practicable. <br /> The hydrostatic pressure from a high water table ' M - <br /> imposes inward pressure on the outer wall of a -- <br /> UST. Applying a vacuum to the interstitial space t`` <br /> of the tank creates additional pressure on the outer < ' <br /> wall. These combined forces can damage the ; <br /> secondary tank wall when there is a large defined <br /> space between the primary and secondary tanks, <br /> Consequently, to prevent damage to the tank it is '+ L <br /> important to observe the water table and associated <br /> recommended vacuum levels when testing. <br /> Vent the primary tank to atmosphere during the FIGURE 4-3. The vacuum gauge and control valve used <br /> test. for tank Interstitial testing. <br /> In some installations the tank interstitial space <br /> may be vented to minimi7.e the buildup of conden- ``` <br /> y P <br /> salon.In these cases,seal off any vent lines to the <br /> tank interstitial space prior to testing. ` <br /> Determine the volume of the tank. This informa- <br /> tion is available from facility records or the auto- 'r p ` <br /> matic tank gauge(ATG)readout. i <br /> 4.2.5 Steel Tanks. Determine if the interstitial ' <br /> space is a"tight wrap"design or a"110%contain- <br /> ment" design. Tanks with a 110% containment <br /> design should use the latest version of Steel Tank <br /> Institute's (STI) Recommended Practice ROJ2, <br /> Recommended Practice for Interstitial 71ghtness <br /> Testing of&xisting Underground Double Wall Steel <br /> Taroks for testing. <br /> For tight wrap tanks, use the test method in this <br /> section. ' <br /> 4.2.6 Fiberglass Tanks. Determine if the inter- <br /> stitial space is a "tight wrap" design or a "110% <br /> containment"design.Either type of fiberglass tank <br /> may use this test, or- the latest version of Fiber- <br /> glass Tank & Pipe Institutes, Field Test Protocol <br /> for Testing the Armtidar Space of Installed Under- FIGURE 4-4. The plumber's plug provides a leak-tight <br /> ground Fiberglass Double and Triple-wall Taroks connection to draw a vacuum on the tank interstitial <br /> with Dry Annular Space, FT&PI 4/01/07. space. <br /> pei.org <br />