PEIIRP1200-12 <br /> there acre items that must be repaired or replaced 6.5.6 Test Procedure. <br /> (e.g., deteriorated penetration fitting boots), L Begin the test by adding water to the sump to a <br /> notify the owner/operator and obtain approval minimum of 4 inches above the highest sump <br /> prior to proceeding with repairs. penetration or sump sidewall seam,whichever is <br /> 4.Test boots or secondary containment termina- higher.To compensate for sump deflection, the <br /> tion fittings must be present on the piping pen- water must be allowed to settle a minimum of <br /> etrating the sunup. During testing, these fittings 15 minutes before taking the initial test measure-- <br /> prevent water from entering the interstitial space meat. If the highest sump penetration or sump <br /> of double-walled piping. Without these fittings, sidewall seam is less than 4 inches from the top <br /> the integrity of the sump cannot be tested using of the sump, add water to within 1 inch of the <br /> this method. top of the sump. <br /> S.If interstitial monitoring sensors are present 2.Place the measuring stick vertically at the lowest <br /> within the containment sumps, temporarily point in the sump and extending above the water <br /> remove them before conducting the test. If the level in the sump to allow for an accurate mea- <br /> sensor is removed, reposition after testing to surement to be taken.The location of the mea- <br /> appropriate position according to the naanufac- suring stick must remain the same for each water <br /> turer's instructions. level measurement. Document the initial water <br /> 6.If the containment sump is found to have cracks, level measurement as measured from the bottom <br /> loose parts or separation of any joints or penetra- of the sump.Alternative measurement methods <br /> tion fittings, it is not considered to be liquid- may be used provided that the measurement to <br /> tight.This visually indicates a test failure. 1116(0.063)inch can be made. <br /> 8.Take all precautions to prevent the water level <br /> CAUTION: Water can damage electrical from being disturbed during the duration of the <br /> connections. Ensure that there are no test. <br /> components that can be damaged by the 4.After 1 hour, document the ending water level <br /> addition of water to the sump. If such measurement. <br /> components are present,take appropriate S.Upon completion of the test: <br /> precautions when performing the test or <br /> use an alternative test method. remove all water and properly dispose of it <br /> according to Section 6.7; <br /> • reinstall any interstitial n onitoiring sensors in <br /> their proper positions; <br /> • return the test boots or secondary contain- <br /> ment fittings to thch-pre-test operating con- <br /> figurations; <br /> water Electrical <br /> Level Jundlon <br /> i Box <br /> r"'t=��`� Electrical <br /> conduit <br /> ?; water <br /> Level <br /> Product <br /> :.• Piping <br /> �- =.'•: I III' <br /> Conduit <br /> Product <br /> FIGURE 6-5. The test fluid level in the UM must be at Pipro9 <br /> least 4 Inches above the highest sump penetration or <br /> sidewall seam. <br /> FIGURE 6.6. To prevent leakage,check all penetration <br /> fittings before adding water to ensure they make a tight <br /> seat. <br /> 0 peLorg <br />