Laserfiche WebLink
TA I T <br />•W-0 1* 14j 4--11 Syr 7A1 N. ?arkemn"r !Drlw, Samra Ana, CA 92705 <br />pr714156019222 www.1imixi m <br />Identification of Test Proceduresfor Secondary Containment Testing <br />To Whom It May Concern: <br />Tait Environmental Services, Inc., utilizes the following procedureswhen conducting Secondary <br />Containment Testing: <br />1) Containment Sumps, Transition Sumps, UDCa—Tait follows PB-RP1200-17 Section 6.6 for the <br />accelerated test method. Tait uses the Incon T&1000 hydrostatic test equipment following the <br />attached procedures. <br />2) dill Buckets; Direct Bury& Contained in Sumps —Spill buckets contained in sumpsare tested <br />per PD-1200-17, Section 6.2, however Tait Pass/Fail threshold is0" drop in one hour. Direct Bury <br />pill Buckets are test the same as containment sumps per PD-1200-17, Section 6.6. <br />3) Tank Annular Space —testing is conducted per PD-1200-17, Section 4.2 <br />4) Piping Secondary Containment —Testing is conducted per PD-RP1200-17, Section 5.3 <br />Please consider this letter as our Test Procedure utilized when conducting Secondary Containment <br />Testing in lieu of either parts or the whole RP1200 document due to copyright infringement. <br />