Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />6. TANK SECONDARY CONTAINMENT TEST <br />Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br />Test Type ❑ Pressure 0 Vacuum ❑ Hydrostatic <br />Test Equipment Used: 4" Dial Gauge (Vacuum) <br />Tank ID <br />UE046u002 <br />Tank Manufacturer <br />Modern Welding <br />Tank Capacity <br />4010 Gallons <br />Test Start Time <br />09:37 AM <br />Initial Reading <br />-10" hg <br />Test End Time <br />10:37 AM <br />Final Reading <br />-10" hg <br />Change in Reading <br />0° hg <br />Pass/Fail Criteria <br />0° hg <br />Tightness Test Results <br />❑✓ Pass ❑ Fail <br />I ❑ Pass ❑ Fail <br />I ❑ Pass ❑ Fail <br />I ❑ Pass ❑ Fail <br />7. PIPE SECONDARY CONTAINMENT TEST <br />Test Method Developed by ❑ Manufacturer ❑✓ Industry Standard ❑ Professional Engineer <br />Test Type ❑✓ Pressure ❑ Vacuum ❑ Hydrostatic <br />Test Equipment Used: 4" Dial Gauge (Pressure) <br />Pipe Run ID <br />Supply/Return <br />Pipe Manufacturer <br />Enviroflex <br />Test Start Time <br />09:37 AM <br />Initial Reading <br />5 psi <br />Test End Time <br />10:37 AM <br />Final Reading <br />0 psi <br />Change in Reading <br />5 psi <br />Pass/Fail Criteria <br />0 psi <br />Tightness Test Results <br />❑ Pass ❑✓ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Pipe Run ID <br />Pipe Manufacturer <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />I ❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Additional copies of this page may be attached. <br />All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 2 of 5 <br />