Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ❑ Hydrostatic <br /> Test Equipment Used:Proteus Ct-D <br /> Sump/UDC ID 87 STP 91STP <br /> Sump Manufacturer Xerxes Xerxes <br /> Sump Depth (inches) 53 56 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 21 22 <br /> (inches) <br /> Test Start Time 10:17 10:17 <br /> Initial Reading 7.993 12.753 <br /> Test End Time 10:32 10:32 <br /> Final Reading 7.993 12.754 <br /> Change in Reading 0.000 0.001 <br /> Pass/Fail Criteria +i-0.002 +i-0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1-2 UDC 3-4 UDC 5-6 <br /> Sump Manufacturer Bravo Bravo Bravo <br /> Sump Depth (inches) 9 9 9 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration Bottom Bottom Bottom <br /> (inches) <br /> Test Start Time 11:05 11:05 11:05 <br /> Initial Reading 1.949 5.771 5.281 <br /> Test End Time 11:20 11:20 11:20 <br /> Final Reading 1.948 5.771 5.281 <br /> Change in Reading 0.001 0.000 0.000 <br /> Pass/Fail Criteria +i-0.002 +i-0.002 +i-0.002 <br /> Tightness Test Results 0 Pass ❑ Fail ❑ Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />