_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> -ipWork Order: 2379677 Date: 5/22/2025 <br /> Site Name/ID. TESORO/SPEEDWAY#68153/43171/4612 <br /> Address: 2448 WEST KETTLEMAN LANE <br /> City: LODI State: CA Zip: 95242 <br /> Tank ID T-1 T-2 T-3 <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 8 8 8 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. 19011542 22121066 19041194 <br /> Pump Operating Pressure(psi) 30.00 40.00 38.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 40.00 38.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 110.00 115.00 110.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 15 15 10 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 5 5 4 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Steve Wil1lAe�ms Certification#: 114537 <br /> Technician Signature: ) Expire Date: 1/5/2026 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />