Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> 87, 91, Diesel East, 87, 91, Diesel West secondary piping, replaced test boots, retested and <br /> passed. <br /> Vapor Return piping failed, needs further investigation. <br /> Vent box, replaced test boots, retested and passed. <br /> UDC's 1/2, 3/4, 5/6, 7/8, 9/10, 11/12, 13/14, 15/16, replaced some test boots and made <br /> adjustments, tightened boots in UDC's. Retested and passed. <br /> No inspector present. <br /> Describe in Section 9 all tests marked "Fail"and any repairs made during the test. Page 4 of 4 <br />