Laserfiche WebLink
,# LDT 5000 Field Test Apparatus Page 1 of 1 <br /> TI�t"l�Lnoiogy Line Leak Detector Test <br /> Work Order: 2391338 Date: 5/14/2026 <br /> Site Name/ID: TESORO/SPEEDWAY#68221 /43208/6187 <br /> Address: 2705 COUNTRY CLUB BLVD <br /> City: STOCKTON State: CA Zip: 95204 <br /> Tank ID 1 2 3 <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 6 6 3 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. Unknown Unknown Unknown <br /> Pump Operating Pressure(psi) 33.00 35.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 33.00 35.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 150.00 140.00 <br /> *N/A for Electronic LD's <br /> Metering PSI 15 18 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 2 3 <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass Not Tested <br /> Technician Comments:SITE HAD ISSUES WITH DSL DISPN.WAS NOT ABLE TO TEST LID ON DSL LINE.WAS CALLED <br /> INTO THE OFFICE <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: f. Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2026 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />