Laserfiche WebLink
,# LDT 5000 Field Test Apparatus Page 1 of 1 <br /> ,ipjTI�f"II�Lf70i y Line Leak Detector Test <br /> Work Order: 2387902 Date: 2/13/2026 <br /> Site Name/ID: 7 ELEVEN 35355/35355 <br /> Address: 3202 W HAMMER LANE(N-136) <br /> City: STOCKTON State: CA Zip: 95209 <br /> Tank ID T1: Regular T2: Premium T3: Diesel <br /> Product RUL PUL Diesel <br /> Product Line 1 1 1 <br /> Tested From 8 8 8 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model FE Petro MLD FE Petro MILD Vaporless LD-2000 <br /> Serial No. UNREADABLE 02070690 05071049 <br /> Pump Operating Pressure(psi) 30.00 30.00 29.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 30.00 29.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 165.00 160.00 180.00 <br /> *N/A for Electronic LD's <br /> Metering PSI 14 13 16 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 5 6 4 <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: f. Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2026 Tanknology Inc.,Austin,Tx. All rights reserved. tanknology.com <br />