Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer El Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used:Incon TS-STS Tester <br /> Sump/UDC ID 87 STP 91 STP UDC 1/2 UDC 314 <br /> Sump Manufacturer Fiberglass Fiberglass Bravo Bravo <br /> Sump Depth (inches) 642 66" 30" 30" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 212 22" <br /> (inches) <br /> Test Start Time 8:09 am 8:09 am 9:22 am 9:22 am <br /> Initial Reading 3.3277 5.1243 6.5577 4.0009 <br /> Test End Time 8:24 am 8:24 am 9:37 am 9:37 am <br /> Final Reading 3.3243 5.1258 6.5569 4.0001 <br /> Change in Reading 0.0034 -0.0015 0.0008 0.0008 <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results ❑ Pass El Fail El Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />