AFF0 A-TEST 209 794 0112 P_02 <br /> INVOICE IJB000375 TEST DATE: 04/08/99 <br /> AFFORDA-TE$T <br /> POB 36 - 26515 N SACRAMENTO BL <br /> THORNTON, CA 95686-0036 <br /> (209)794-0102 FAX (209)794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> STOCKTON SERVICE STATION SAN JOAQUIN CO. CORP. YARD <br /> P.O. BOX 508 1810 HAZELTON ST. <br /> $08 N. UNION ST. <br /> STOCXTON, CA. STOCKTON, CA. <br /> 95201 <br /> CONTACT: HENDF:RSON, MARK <br /> PHONE #: (209)464--8333 <br /> ***** COMMENT LINES ***** <br /> TWO 151( TANKS - T-1 RUL - T-2 DIE - PRESSURE SYSTEM <br /> BALANCED VR ON GAS W/VEEDER-ROOT TLS-350 ATG <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND FUEL TANKS, THE <br /> THE MAXIMUM ALLOWABLE HOURLY LEAK/GAIN RATE IS .05 GALLONS. <br /> ULLAGE TESTS ARE ON A PASS/FAIL BASIS ONLY. <br /> TANK #X: REG UNLEADED TYPE: E-CLASS RATE: .008420 G.F.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: .65 <br /> TANK IS TIGHT. <br /> TANK #2: DIESEL FUEL 2 TYPE: E-GLASS RATE: .019977 G.P.H. LOSS <br /> ULLAGE-.PASS SIGNAL/NOISE: .15 <br /> TANK IS TIGHT. <br /> EQUIPMENT:USTEST <br /> OTTL #97-1143 <br /> OPERATOR: LYLE D. NIMMO y1� TATtE: <br /> DAVID WINKLER, Trainee J <br />