Laserfiche WebLink
Underground Storage Tank <br /> Release Detection Equipment Testing Report Form <br /> 8. COMMENTS <br /> Describe all answers marked "No"or "Fail"and proposed remedy. <br /> List all release detection equipment either replaced or repaired (including cleaning or adjustment). <br /> AT THIS TIME WE ARRIVED AND SITE HAS AN ALARM " Q 1 LINE EQUIP FAULT ALARM" <br /> LEAK DETECTOR DIE NOT TESTED. <br /> ALL OTHER TESTING WAS GREAT. <br /> SO WE STARTED TROUBLESHOOTING ALARM, INSTALLED NEW ELECTRONIC L/D, <br /> WE FOUND THAT THE WIRING BETWEEN THE TLS AND THE TURBINE HAS EXPIRED. <br /> THE SENSOR IN THE TURBINE MAY STILL BE GOOD, HOWEVER THE WIRING BETWEEN <br /> NEEDS TO BE REPLACED. THE OTHER OPTION FOR THE DIESEL LEAK DETECTOR IS TO <br /> CHANGE THIS ONE OUT TO MECHANICAL UNTIL TLS IS UPGRADED TO A 450 VERSION. <br /> Describe all answers marked "No"or "Fail"and the proposed remedy in Section 8. <br /> List all equipment either replaced or repaired (including cleaning or adjustment) in Section 8. <br /> Page 5 of 6 <br />